Snapshot data points

displayed on the
Current Data

page

contain timestamps

that are not being

updated:

Check the status of Data Collection on the Home page.
Navigate to Time Source > Controller in the web interface.

Check for a message that indicates that data collection has

discarded data.
If Data Collection status is “Running”, check the Collection

Rate in the System Status section in the left navigation bar.

Ensure that the Collection

Rate is zero; this confirms

that Data Collection is not

collecting data.

Go to the Web Diagnostics
Firmware

tab, and check

the Data Sever page. N/A

indicates an error state.

Reboot the module.

If Data Collection stops

again, go to the Configure
Historian

tab, and click

Data Storage.

Ensure that

the Archive Disk Threshold

and Archive Usage Thresh-

old are still valid. If these

thresholds have been

reached, wait for the system

to process overflow events

and return to a state that

allows you to restart Data

Collection.

If the Collection Rate is not

zero, check the status of the

Data Server on the Home

page.

If the Point Server status is

“Stopped” or “Error”,

reboot the module.

If the Data Collection status is “Stopped”, go to the Data
Collection

page and restart Data Collection.

A single point has not

collected data for a

significant time

period:

Check the point configuration on the Point Property page.

Ensure that the scan rate is not set too low, and ensure that

the Exception and Compression values are configured

properly for the point.

Data Collection

Symptom

Solution