Configure Module Messaging 91

last HART message initiated or the handle selected by the "Select Handle"
message whichever occurred the most recent.

Message Setup Parameters

Field

Value

Definition

Message Type

"CIP Generic"

Service Type

Get Attribute Single

Read From Module

Service Code

0x0E

Class Name

0x7D

FLEX Module Object

Instance

1…8 (Module next to Adapter = 1)

Module Location

Object Attribute

0x80

Get Status

Reply Size

6 bytes

Request Size

0

Request Packet Data Structure

Offset

Field

Value

Definition

0

Query Status

0…5

Status of Command
related to Handle

1

Channel

0…7 (Handle Active)
0xFF (Handle not active)

Channel associated with
Status

2

Handle

0…255

Message Handle Echo

3

Next Assembly Attribute
OR
HART Failed Reason
Code if Query Status = 3

0x81…0x86

1…0x88 HART Failed
Reason Code

Recommended assembly
to read next else returns
0 if this is the last page.
If Query Status is equal
to 3, then this value is
the Failed Reason Code.

4…5

Total Bytes in Reply

0…264 (16 bit Word)

Total bytes available in
reply excluding the 8
bytes of header
information returned in
each read request
(page).

Query Status:

0 = Success - Data Available (retrieve reply by reading next assembly index)
1 = No Data/Message Active. Handle requested not associated with any active
message.
2 = Running - Data reply is not available yet
3 = HART Request Failed (See Reason Code in byte 3)
4 = Incomplete Message Request-Not enough data received yet
5 = Handle already in use.