Remote low low alarm limit (8 of 16 bit) – Rockwell Automation 1794-OF8IH FLEX Isolated Input/Output HART Analog Modules User Manual

Page 53

Advertising
background image

Publication 1794-UM065B-EN-E - September 2010

1794-IF8IH and 1794-OF8IH Configuration 41

Remote Low Low Alarm Limit (8 of 16 bit)

Sets the limit for the Remote Fault Low Low Alarm in 1

μ

A steps. This affects

Data Formats 0…7. Steps apply to the 4…20 mA range.

For example, a value of 3600 will cause a Remote Fault Low Low Alarm below
3.6 mA (3600*1

μ

A=3.6 mA).

Range: 0…22000 (0=disabled, 1*1

μ

A to 22000*1

μ

A)

Default: 0=disabled
Data Table Reference: Remote Low Low Alarm Limit, Configuration Words
12, 16, 20, 24, 28, 32, 36 and 40, bits 0…15

5

4…20 mA
as %

0.16% of
4…20 mA

2…22 mA

-1250 … +11250
(2’s complement)
(-12.50% …
+112.50%)

625/
1.6 µA

6

Not Assigned

7

4…20 mA
as unsigned
integer

0.03% of
4…20 mA

4…20 mA

0…65535
(4…20 mA)

4095/
0.2441 µA

8

0…20 mA

Not Assigned

9

0…20 mA

Not Assigned

10

0…20 mA

Not Assigned

11

0…20 mA

Not Assigned

12

4…20 mA

Not Assigned

13

4…20 mA

Not Assigned

14

4…20 mA

Not Assigned

15

4…20 mA

Not Assigned

1794-IF8IH Data Formats

Data
Format

Format

Resolution

Input Range

Module Data Processing

Data Table Value
(Interpretation)

Count per mA/
Resolution

Datatable = 10000

input-4

(

16

)

Datatable = 65535

input-4

(

16

)