Rockwell Automation 1794-OF8IH FLEX Isolated Input/Output HART Analog Modules User Manual

Page 46

Advertising
background image

Publication 1794-UM065B-EN-E - September 2010

34 1794-IF8IH and 1794-OF8IH Configuration

1794-IF8IH Channel Data Formats

Format

(1)

Bits

Format Name

Signal Range

User Range

Resolution

15 14 13 12

11 10 9

8

7

6

5

4

LO

HI

LO

HI

3

2

1

0

0

0

0

0

0

0…20 mA in Milliamps

0.00

22.00

0 (0.000 mA)

22000 (22.000 mA)

1.0 µA

1

0

0

0

1

0…20 mA in % Full Scale 0.00

22.00

0 (0%)

11000 (110.00%)

2.0 µA

3

0

0

1

1

0…20 mA in UINT

0.00

20.00

0

65535

0.3052 µA

4

(2)

0

1

0

0

4…20 mA in Milliamps

2.00

22.00

2000 (2.000 mA)

22000 (22.000 mA)

1.0 µA

5

(2)

0

1

0

1

4…20 mA in % Full Scale 2.00

22.00

-1250 (-12.50%)

11250 (112.50%)

1.6 µA

7

(2)

0

1

1

1

4…20 mA in UINT

4.00

20.00

0

65535

0.2441 µA

(1)

All other formats are invalid.

(2)

HART Communications supported with these data formats only.

1794-IF8IH Channel Digital Filter

Digital Filter frequency Decimal

Value

Bits

10

9

8

2

1

0

470 Hz

0

0

0

0

62 Hz

1

0

0

1

19.6 Hz

2

0

1

0

16.7 Hz

3

0

1

1

10 Hz

4

1

0

0

4.17 Hz

5

1

0

1

Not applicable

6

1

1

0

Not applicable

7

1

1

1

1794-IF8IH HART Current Ratio

HART Current
Ratio Limit

Decimal
Value

Bits

15

14

13

12

11

7

6

5

4

3

Disabled

0

0

0

0

0

0

Not applicable

1

0

0

0

0

1

Not applicable

2

0

0

0

1

0

Not applicable

3

0

0

0

1

1

Not applicable

4

0

0

1

0

0

5%

5

0

0

1

0

1

Advertising