Local fault mode – Rockwell Automation 1794-OF8IH FLEX Isolated Input/Output HART Analog Modules User Manual

Page 22

Advertising
background image

Publication 1794-UM065B-EN-E - September 2010

10 Configurable FLEX I/O Analog Module Features

Select Your Analog Output
Module Operating Features

All features of the 1794-OF8IH analog output module are independently
configurable.

Local Fault Mode

The Local Fault Mode can be programmed to determine how the module
responds to communications faults and internal module faults.

When setting the Local Fault Mode feature in your programming software, set
this feature’s bit to 0 to use the analog fault state or digital fault state only if a
communications fault occurs. Set the bit to 1 to use the Analog Fault state or
Digital Fault state if any fault occurs.

7

4…20 mA
as unsigned
integer

0.03% of
4…20 mA

0…65535
(4…20 mA)

4095

With
error
steps

8

Not assigned

9

10

11

0…20 mA
as A/D
count

0.04% of
0…20 mA

0…22 mA

0…55000
(0…22 mA)

2500

All
fixed

12

4…20 mA
as %

0.16% of
4…20 mA

3.6…21 mA

-250 … +10625
(2’s complement)
(-2.50…+106.25%)

625

NAMU
R NE 4
all fixed

13

4…20mA
as %

0.16% of
4…20 mA

3…21 mA

-625 … +10625
(2’s complement)
(-6.25…+106.25%)

All
fixed

14

4…20 mA
as %

0.16% of
4…20 mA

2…22 mA

-1250 … +11250
(2’s complement)
(-12.50…+112.50
%)

15

Not assigned

1794-IF8IH Data Formats

Data
Format

Format

Resolution

Input
Range

Module Data Processing

Data Table Value
(Interpretation)

Count
per mA

Error
Steps

input-4

(

16

)

Datatable = 65535

input

(

22

)

Datatable = 55000

input-4

(

16

)

Datatable = 10000

input-4

(

16

)

Datatable = 10000

input-4

(

16

)

Datatable = 10000

IMPORTANT

The default selection value for all parameters is 0.