Publication 1794-UM065B-EN-E - September 2010

Configure Module Messaging 79

Enable Publishing HART Command 3 Variables

In the module configuration tag "ChXHARTCmd3Disable", make sure the
value is "0" for each channel that is connected to a HART device.

Accessing HART Data Using CIP Message Instruction (MSG)

The 1794-IF8IH and 1794-OF8IH modules support these broad categories of
MSG based HART access:

• CIP formatted messages to retrieve common HART data cached in the

module.

• CIP messages containing HART formatted commands that are passed

directly to the HART Field Device for processing. These are called Pass
through messages.

Fill in The Information Needed for a MSG Instruction

The "MSG" instruction is formatted as shown below.

IMPORTANT

If you previously selected "Input Data" for the Comm Format because
you are not using the HART Variables in your control system then set
all channels of the "ChXHARTCmd3Disable" configuration tag to "1"
for the best pass through messaging and Asset Management
Software performance.

CIP Message Format – Unconnected Message Header

Field

Value

Definition

Message Type

"CIP Generic"

Service Code

0x0E Get Attribute Single-READ DATA
0x10 Set Attribute Single-WRITE DATA

Class Name

0x007D

FLEX module object

Instance Name

1…8

Module location
1 = module adjacent to
adapter

Object Attribute

0x7E…0xA7

Selects Data Assembly or
function
(see Module Data Access
Assemblies)

Source Length
(applies to Set
Attribute
Single)

Depends on data assembly selected

Specifies size in bytes of
data to write to module