Publication 1794-UM065B-EN-E - September 2010

Configurable FLEX I/O Analog Module Features 13

Fault Alarm

Fault Alarm selects whether the channel fault detection is enabled or disabled.
There is a 100 Hz (10 ms) filter for wire off or lead break detection.

Use your programming software to set the Fault Alarm. Set the feature bit to 0
to disable the alarm. Set the bit to 1 to enable wire off/lead break fault
detection.

Understand Image Table
Mapping and Bit/Word
Descriptions

All Allen Bradley FLEX I/O modules have a sixteen word table of Real Time
Data (RTD) to be transferred between the controller and the I/O module.

4

mA as
4…20 mA

0.1% of
4…20 mA

2…22 mA

2000…22000
(2.000…22.000 mA)

1000/
1.0 µA

Min=2 mA
Max=22 mA
hold
Last=hold
FS value

5

4…20 mA

4…20 mA Not assigned

6

4…20 mA

4…20 mA Not assigned

7

Unsigned
integer as
4…20 mA

0.03% of
4…20 mA

4…20 mA

0…65535
(4…20 mA)

4095/
0.244 µA

Min=4 mA
Max=20 mA
hold
Last=hold
FS value

8

0…20 mA

0…20 mA Not assigned

9

0…20 mA

0…20 mA Not assigned

10

0…20 mA

0…20 mA Not assigned

11

0…20 mA

0…20 mA Not assigned

12

4…20 mA

Not assigned

13

4…20 mA

Not assigned

14

% as
4…20 mA

0.16% of
4…20 mA

2…22 mA

-1250 … +11250
(2’s complement)
(-12.50% …
+112.50%)

625/
1.6 µA

Min=2 mA
Max=22 mA
hold
Last=hold
FS value

15

4…20 mA

4…20 mA Not assigned

1794-OF8IH Data Formats

Data
Format

Format

Resolution Full

Output
Range

Module Data Processing

Data Table Value
(Interpretation)

Count per
mA/
Resolution

Analog Fault
State

Output =

datatable

(

1000

)

Output = 16

datatable

(

65535

)

+ 4

Output = 16

datatable

(

10000

)

+ 4