14 Configurable FLEX I/O Analog Module Features

Not all 16 words need be allocated. The 1794-IF8IH has the following RTD
I/O Profile:

Chapter Summary

In this chapter, we told you about the FLEX I/O system and the analog I/O
modules, and how they communicate with programmable controllers. Move
on to the next chapter to learn how to install your FLEX I/O analog module.

1794-IF8IH RTD I/O Profile

RTD Index

Assembly Index

Assembly

RTD 0

MSW

Module Status Word

RTD 1

EDT Read Word

EDT Read Word

RTD 2…9

I:0…I:7

RTD Input Data

1794-IF8IH Analog data table

Word

Bit
15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

Channel 0 Input Data

1

Channel 1 Input Data

2

Channel 2 Input Data

3

Channel 3 Input Data

4

Channel 4 Input Data

5

Channel 5 Input Data

6

Channel 6 Input Data

7

Channel 7 Input Data

8

H7

H6

H5

H4

H3

H2

H1

H0

L7

L6

L5

L4

L3

L2

L1

L0

9

R7

R6

R5

R4

R3

R2

R1

R0

P7

P6

P5

P4

P3

P2

P1

P0

10

Reserved

Diagnostic Status

11

C7

C6

C5

C4

C3

C2

C1

C0

F7

F6

F5

F4

F3

F2

F1

F0

12

X7

X6

X5

X4

X3

X2

X1

X0

Reserved

Where:

Hn: Channel n High Alarm
Ln: Channel n Low Alarm
Pn: Channel n Out Of Range Alarm
Rn: Channel n Second (Remote) Alarm
Fn: Channel n HART Failure
Cn: Channel n HART Current Fault
Xn: Channel n HART Transmitter Present

0: False 1: True