Install Your FLEX I/O Analog Modules

Overview

Read this chapter to install the input and output analog modules.

Before You Install Your
Analog Module

Before installing your FLEX I/O analog module:

Removal and Insertion
Under Power

Topic

Page

Before You Install Your Analog Module

15

Removal and Insertion Under Power

15

Install the Module

16

Wire the Terminal Base Units

22

Connect Wiring to the FLEX I/O HART Analog Modules

22

Ground the Module

24

Chapter Summary

24

Steps to Complete Before Installation

You Need To

As Descibed Under

Verify that the module will be installed in a
suitable enclosure

Removal and Insertion Under Power,
page 17

Position the keyswitch on the terminal base

Install the Module, page 18

ATTENTION

These modules do not receive primary operational power from the
backplane. +V and -V DC power must be applied to your module
before installation. If power is not applied, the module position will
appear to the adapter as an empty slot in your chassis.

WARNING

These module are designed so you can remove and insert them under
power. However, take special care when removing or inserting these
modules in an active process. I/O attached to any module being
removed or inserted can change states due to its input/output signal
changing conditions.

If you insert or remove the terminal base while backplane power is on,
an electrical arc can occur. This could cause an explosion in hazardous
location installations.

Be sure that power is removed or the area is nonhazardous before
proceeding.