Publication 1794-UM065B-EN-E - September 2010

76 1794-IF8IH and 1794-OF8IH Configuration

The Module supports six states, common to all Phase 1 EDT compliant
modules, as described below. A single bi-color indicators the module status as
indicated below.

Chapter Summary

In this chapter, you learned how to configure your HART module and how to
use the RSLogix software to install and configure your module. The next
chapter describes how to configure your module to automatically collect data
from the HART field device and place it in the module's Input Tag.

Module Status Indicators

Module
State

Condition

PU Bit

Prog/Run bit

Fault bit

LED Color and
State

New

Power up initialized complete and passed Self-Test.
Loads stored configuration, if it exists. Read Module
Information Block.

(1)

*

(2)

*

*

Red, blink @ 1 Hz

No Config

Module has not received configuration from Master.
It can Set and Get attributes.

0

*

*

Green, blink @ 1 Hz

Idle

Controller in Program mode.
Communications normal

1

0

1

Green, blink @ 1 Hz

Active

Controller in Run mode & Communication Is normal

1

1

1

Green, solid

Fault

FLEX I/O Comm. Fault or PU bit is one and /Fault=0

*

*

0

Green, blink@ 1 Hz

Fatal fault

Module fails self tests or detects illegal state
transition

*

*

*

Red, solid

Off

External power has not been applied.

Off

(1)

The status bits in the table correspond to module status bits available in the module status word.

(2)

Bit state flagged as '*' depends on the state transition, per FLEX I/O Systems Specifications.