Publication 1794-UM065B-EN-E - September 2010

54 1794-IF8IH and 1794-OF8IH Configuration

Data Table Reference: CMD3 Comm Status, Secondary Input Word 0
bits 0…7.

HART Field Device Command and Communication Status (8 of 8
bits)

This byte indicates the status of HART FD communication for the channel. It
is the first status byte of the HART response and the FD status, example:
"parity error", "framing error", "invalid selection" or "too few data bytes
received" is coded in.

Data Table Reference: HART Comm Status, Secondary Input Word a,
bits 0…7.

HART Field Device Status (8 of 8 bits)

This byte is part of the CMD 3 data response of the HART FD. It is the
second status byte of the HART response and the FD status, example:
"primary variable out of limits" or "analog output saturated" is coded in.

Data Table Reference: HART Field Device Status, Secondary Input Word a,
bits 8…15.

CMD3 2nd status byte response codes

HART Field Device Status

Bit 0

Primary variable out of limits

Bit 1

Non-primary variable out of limits

Bit 2

Analog output saturated

Bit 3

Analog output current fixed

Bit 4

More status available

Bit 5

Cold start

Bit 6

Configuration changed

Bit 7

Field device malfunction

IMPORTANT

All bits "0" (when a communication error is reported in the
CMD3 1st status byte)