122 Use the 1794-IF8IH Module with the Generic Profile

4

[Adapter Name]:[Slot]:C.Data[3].0

[Adapter Name]:[Slot]:C.Data[3].1

[Adapter Name]:[Slot]:C.Data[3].2

[Adapter Name]:[Slot]:C.Data[3].3

5

[Adapter Name]:[Slot]:C.Data[3].4

[Adapter Name]:[Slot]:C.Data[3].5

[Adapter Name]:[Slot]:C.Data[3].6

[Adapter Name]:[Slot]:C.Data[3].7

6

[Adapter Name]:[Slot]:C.Data[3].8

[Adapter Name]:[Slot]:C.Data[3].9

[Adapter Name]:[Slot]:C.Data[3].10

[Adapter Name]:[Slot]:C.Data[3].11

7

[Adapter Name]:[Slot]:C.Data[3].12

[Adapter Name]:[Slot]:C.Data[3].13

[Adapter Name]:[Slot]:C.Data[3].14

[Adapter Name]:[Slot]:C.Data[3].15

Channel

Bits

Channel Data Formats

Format

(1)

Bits

Format Name

Signal Range

User Range

Resolution

15 14 13 12

11 10 9

8

7

6

5

4

LO

HI

LO

HI

3

2

1

0

0

0

0

0

0

0…20 mA in Milliamps

0.00

22.00

0
(0.000 mA)

22000
(22.000 mA)

1.0 µA

1

0

0

0

1

0…20 mA in % Full Scale

0.00

22.00

0
(0%)

11000
(110.00%)

2.0 µA

3

0

0

1

1

0…20 mA in UINT

0.00

20.00

0

65535

0.3052 µA

4

(2)

0

1

0

0

4…20 mA in Milliamps

2.00

22.00

2000
(2.000 mA)

22000
(22.000 mA)

1.0 µA

5

(2)

0

1

0

1

4…20 mA in % Full Scale

2.00

22.00

-1250
(-12.50%)

11250
(112.50%)

1.6 µA

7

(2)

0

1

1

1

4…20 mA in UINT

4.00

20.00

0

65535

0.2441 µA

(1)

All other formats are invalid.

(2)

HART Communications supported with these data formats only.