Additional HART Protocol Information 107

11

Read unique identifier
associated with tag

0…5

Tag

(A)

0…11

As Command 0

12

Read message

None

0…23

Message (32 characters)

(A)

13

Read tag descriptor,
date

None

0…5

Tag (8 characters)

(A)

6…17

Descriptor (16 characters)

(A)

18…20

Date

(D)

14

Read PV sensor
information

None

0…2

Sensor serial number

3

Units code for sensor limits and
minimum span

4…7

Upper sensor limit

(F)

8…11

Lower sensor limit

12…15

Minimum span

15

Read output
information

None

0

Alarm select code

1

Transfer function code

2

PV/range limits code

3…6

Upper range value

7…10

Lower range value

11…14

Damping value (seconds)

(F)

15

Write protect code

16

Private-label distributor code

16

Read final assembly
number

None

0…2

Final assembly number

17

Write message

0…23

Message (32
characters)

(A)

As in command

18

Write tag descriptor,
date

0…5

Tag (8
characters)

(A)

As in command

6…17

Descriptor (16
characters)

18…20 Date

(D)

19

Write final assembly
number

0…2

Final assembly
number

As in command

(1)

Bit 2 = protocol bridge device.

(2)

Bit 0 = multisensor device, bit 1 = EEPROM control required.

(3)

Truncated after last supported variable.

Universal Commands

Command

Data in Command

Data in Reply

#

Function

Byte

Data

Type

Byte

Data

Type