FLEX I/O HART Module Commands 99

Device-specific Commands

Device-Specific HART Module Commands

Command

Action

Meaning

128

Read

Read parameter assignment of
the multiplexer

The current parameter assignment is read from the multiplexer

129

Read loop status

The status of the current loop can be read with this command. The following
information is supplied:

•Hardware fault

•Rebuild running for this loop

•SCAN activated for this loop

•Searching for the transmitter because it has disappeared

•Transmitter not responding (disappeared)

•Transmitter responding again (appeared)

•Another one responded instead of it (mismatched)

130

Transmitter list

The address of the transmitters that were recognized on the current loops are
returned

131

Read

Read static data of transmitters

For the given long frame addresses, the function returns the following transmitter
data:

•Current loop number, 0…15

•Polling address

•Supported HART revision

•Minimum count of required preambles, 5…20

132

Write

Write static data of transmitters

Write static data (see bit 131). A preamble length outside of the range 5…20 is set
to 5 or 20

133

Delete transmitters from the
transmitter list

Transmitters with the given long frame addresses are removed from the transmitter
list and the SCAN list

134

Read

Read SCAN list

The extended addresses of the transmitters are returned

135

Read dynamic data of
transmitters

For the given long frame addresses, the function returns the following transmitter
data:

•Selected SCAN command

•Long frame address

•HART data

136

Read SCAN status of the
transmitters

For the given long frame addresses, this command returns the SCAN status of the
transmitters (0 = SCAN disabled, 1 = SCAN enabled)

137

Write

Write SCAN status of the
transmitters

For the given long frame addresses, this command sets the SCAN status of the
transmitters (0 = disable SCAN, 1 = enable SCAN)

138

Read

Read error overview of the
transmitters

Thou slain returns ORed communication errors and ORed status bits

139

Write

Delete fault overview of
transmitters

This command returns the OR combination of communication errors and status