Get device info block 3 message – Rockwell Automation 1794-OF8IH FLEX Isolated Input/Output HART Analog Modules User Manual

Page 97

Advertising
background image

Publication 1794-UM065B-EN-E - September 2010

Configure Module Messaging 85

Get Device Info Block 3 Message

Get Device Information Block 3 Message - Request Packet Structure

Field

Value

Definition

Message Type

"CIP Generic"

Service Type

Get Attribute Single

Read From Module

Service Code

0x0E

Class Name

0x7D

FLEX Module Object

Instance

1…8 (Module next to Adapter = 1)

Module Location

Object Attribute

0x89 = Channel 0 (Add 4 for next channel)
0x8D = Channel 1
0x91 = Channel 2
0x95 = Channel 3
0x99 = Channel 4
0x9D = Channel 5
0xA1 = Channel 6
0xA5 = Channel 7

Selects Channel that the
data is from

Reply Size

16 bytes

Request Size

0

Get Device Information Block 3 Message – Reply Packet Structure

Offset

(1)

Field

Value

Definition

0

Status

00 = SUCCESS
0x86 = Channel is not
HART Enabled
0x87 = No Device Found

Command status

1

Echo of Channel

0…7

Channel

2

pad

0

3

pad

0

4

PVAssignmentCode (1 byte)

CMD#50, Byte 0; Set to 0xff
if HART Cmd 50 not
supported by device

5

SVAssignmentCode (1 byte)

CMD#50, Byte 1; Set to 0xff
if HART Cmd 50 not
supported by device

6

TVAssignmentCode (1 byte)

CMD#50, Byte 2; Set to 0xff
if HART Cmd 50 not
supported by device

7

FVAssignmentCode

(1 byte)

CMD#50, Byte 3; Set to 0xff
if HART Cmd 50 not
supported by device

8

PVUnits

(1 byte)

CMD#3, Byte 4; Set to 0 if
device does not return a
value for PV.