Data format – Rockwell Automation 1794-OF8IH FLEX Isolated Input/Output HART Analog Modules User Manual

Page 21

Advertising
background image

Publication 1794-UM065B-EN-E - September 2010

Configurable FLEX I/O Analog Module Features 9

Data Format

You must choose a module data format in your user program. Formats 8, 9, 10
and 15 are not used. If they are selected for a channel quad, a configuration
fault will occur and will be reported as Diagnostic Data 2. All data for that
channel quad will be set to zero (0).

Formats 5, 12, 13 and 14 are 2’s complement data formats, and will return data
in that form.

12 Formats are available

Default format is 0

20 mA

The data format selected interprets input readings and returns them to the
PLC.

1794-IF8IH Data Formats

Data
Format

Format

Resolution

Input
Range

Module Data Processing

Data Table Value
(Interpretation)

Count
per mA

Error
Steps

0

0…20 mA
as mA

0.1 % of
0…20 mA

0…22 mA

Datatable = 1000 (input)

0…22000
(0…22.000 mA)

1000

With
error
steps

1

0…20 mA
as %

0.2 % of
0…20 mA

0…22 mA

0…11000
(0…110.00%)

500

2

0…20 mA
as

%

0.19 % of
0…20 mA

0…22 mA

0…10488
(0…104.88%)

524

3

0…20 mA
as unsigned
integer

0.03 % of
0…20 mA

0…20 mA

0…65535
(0…22 mA)

3276

4

4…20 mA
as mA

0.1 % of
4…20 mA

2…22 mA

Datatable = 1000 (input)

2000…22000
(2.000…22.000
mA)

1000

5

4…20 mA
as %

0.16 % of
4…20 mA

2…22 mA

-1250…+11250
(2’s complement)
(-12.50%…+112.5
0%)

625

With
error
steps

6

4…20 mA
as

%

0.17 % of
4…20 mA

4…22 mA

0…10607
(0…106.07%)

With
error
steps,
under-r
ange
not
allowed

input

(

20

)

Datatable = 10000

Datatable = 10000

input

20

IF...Square_Root_Threshold

< 10000

input

20

Else...datatable = 0

input

(

20

)

Datatable = 65535

input-4

(

16

)

Datatable = 10000

Datatable = 10000

IF...Square_Root_Threshold

< 10000

Else...datatable = 0

input-4

16

input-4

16