12 Configurable FLEX I/O Analog Module Features

• If on the other hand, the configuration had been changed, from the

default, and then it was changed again to a non-assigned format, then
the diagnostic bit 2 for configuration failure is set and the module goes
to the fault state for the last valid configuration.

• Formats 13 and 14 are 2’s complement data formats, and require data to

the module in that form.

• Range: 0…15
• Default: 0
• Data Table Reference: data format, word 12 and 13, bits 0…3, bits 4…7

If data is sent to the module which is out of range, the value will be clipped
and Diagnostic Data will be set to 11 data out of range.

Example of Analog Format 14 and Data Clipping Performance.

1794-OF8IH Data Formats

Data
Format

Format

Resolution Full

Output
Range

Module Data Processing

Data Table Value
(Interpretation)

Count per
mA/
Resolution

Analog Fault
State

0

mA as
0…20 mA

0.1% of
0…20 mA

0…22 mA

0…22000
(0…22.000 mA)

1000/
1.0 µA

Min=0 mA
Max=22 mA
hold
Last=hold
FS value

1

% as
0…20 mA

0.2% of
0…20 mA

0…22 mA

0…11000
(0…110.00%)

500/
2.0 µA

Min=0 mA
Max=22 mA
hold
Last=hold
FS value

2

0…20 mA

0…22 mA Not Assigned

3

Unsigned
integer as
0…20 mA

0.03% of
0…20 mA

0…20 mA

0…65535
(0…20 mA)

3276/
0.305 µA

Min=0 mA
Max=20 mA
hold
Last=hold
FS value

Diagnostic Data error 11
= data out of range

Diagnostic Data error 11
= data out of range

0

4

8

12

16

20

24

Output mA

datatable

20.000

16.000

12.000

8.000

4.000

0.000

-4.000

Output =

datatable

(

1000

)

Output = 20

datatable

(

10000

)

Output = 20

datatable

(

65535

)