98 FLEX I/O HART Module Commands

Universal Commands

Common Practice
Commands

Universal HART Module Commands

Command

Action

Meaning

0

Read

Read unique device
identification

Twelve-byte device identifiers are given in the response

1

Read HART variables (process
values)

Commands are only supported for compatibility purposes and are without any
meaning

The transmitters, namely the SCAN function, have the following functions.

•Read primary variable

•Read primary variable as current (in mA) and percent range)

•Primary variable is read as a current (in mA) and four predefined dynamic

variables

2

3

11

Read unique identifier
associated with tag

The response is a twelve-byte device identifier if the given tag matches the tag of
the multiplexer

12

Read message

Read the 32-bit message (also see bit 17)

13

Selection switch markings in
hand, read description and date

Read the eight-digit selection switch marking (tag) and the 16-digit time and date

17

Write

Write message

The 32-digit message is written (also see bit 12)

18

Write tag, description, and date

Save an 8-digit (tag), a 16-digit description and date

Common Practice HART Module Commands

Command

Action

Meaning

38

Write

Reset configuration changed
flag

Delete status information

41

Perform device self-test

Performs the device self-test similar to turning on the power supply

If no error occurs, the malfunction status message is deleted (if it had been set)

42

Perform device reset

Immediately after the command is confirmed, a reset of the device HART
processor is performed

48

Read

Read additional device status