Publication 1794-UM065B-EN-E - September 2010

Configure Module Messaging 93

Format a "Read Pass through Reply" Request

This message returns the status of pass through message along with the actual
reply from the device if the pass through is completed. The handle associated
with the response data is either the last HART message initiated or the handle
selected by the "Select Handle" message whichever occurred the most recent.

IMPORTANT

Message replies are held by the module until either the
message is retrieved or a 50 second timeout has expired.

If a message has multiple pages, each page must be sent
within 50 seconds of each other until all pages are sent else
the module will discard the whole message and make the
message queue available for the next new requested
message.

If the device does reply to the Pass through request but
reports a problem with the HART command selected in EASY
HART format then the Query Status is 3 (Failed) but in the
FULL HART Protocol format the reply from the device are
returned and the Query Status is 0 (Success).

Unconnected Message

Field

Value

Definition

Message Type

"CIP Generic"

Service Type

Get Attribute Single

Read from Module

Service Code

0x0E

Class Name

0x7D

FLEX Module Object

Instance

1…8 (Module next to Adapter = 1)

Module Location

Object Attribute

0x81…0x86

Get Status

Reply Size

8…48 bytes

(1)

(1)

depends on attribute selected

Request Size

0

Data Response Packet Structure

Offset

Field

Value

Definition

0

Query Status

0…5

Status of Command related to Handle

1

Channel

0…7 (Handle active)
0xFF (Handle not active)

Channel associated with Status

2

Handle

0…255

Message Handle