Get device info block 4 message – Rockwell Automation 1794-OF8IH FLEX Isolated Input/Output HART Analog Modules User Manual

Page 98

Advertising
background image

Publication 1794-UM065B-EN-E - September 2010

86 Configure Module Messaging

Get Device Info Block 4 Message

9

SVUnits

(1 byte)

CMD#3, Byte 9; Set to 0 if
device does not return a
value for SV.

10

TVUnits

(1 byte)

CMD#3, Byte 14; Set to 0 if
device does not return a
value for TV.

11

FVUnits

(1 byte)

CMD#3, Byte 19; Set to 0 if
device does not return a
value for FV.

12

PVRangeUnits

(1 byte)

CMD#15, Byte 2

13

Pad_8 alignment

(1 byte)

14

HARTPreamble

(1 byte)

CMD#0, Byte 3

15

HARTFlages

(1 byte)

CMD#0, Byte 8

(1)

Data in offsets 4…15 will be set to 0 if Status in offset 0 indicates a problem (Status = 0x86 or 0x87).

Get Device Information Block 4 Message – Request Packet Structure

Field

Value

Definition

Message Type

"CIP Generic"

Service Type

Get Attribute Single

Read From Module

Service Code

0x0E

Class Name

0x7D

FLEX Module Object

Instance

1…8 (Module next to Adapter = 1)

Module Location

Object Attribute

0x8A = Channel 0 (Add 4 for next channel)
0x8E = Channel 1
0x92 = Channel 2
0x96 = Channel 3
0x9A = Channel 4
0x9E = Channel 5
0xA2 = Channel 6
0xA6 = Channel 7

Selects Channel that the
data is from

Reply Size

38 bytes

Request Size

0

Get Device Information Block 3 Message – Reply Packet Structure

Offset

(1)

Field

Value

Definition