Get device info block 2 message – Rockwell Automation 1794-OF8IH FLEX Isolated Input/Output HART Analog Modules User Manual

Page 96

Advertising
background image

Publication 1794-UM065B-EN-E - September 2010

84 Configure Module Messaging

Get Device Info Block 2 Message

Get Device Information Block 2 Message – Request Packet Structure

Field

Value

Definition

Message Type

"CIP Generic"

Service Type

Get Attribute Single

Read From Module

Service Code

0x0E

Class Name

0x7D

FLEX Module Object

Instance

1…8 (Module next to Adapter = 1)

Module Location

Object Attribute

0x88 = Channel 0 (Add 4 for next channel)
0x8C = Channel 1
0x90 = Channel 2
0x94 = Channel 3
0x98 = Channel 4
0x9C = Channel 5
0xA0 = Channel 6
0xA4 = Channel 7

Selects Channel that the
data is from

Reply Size

56 bytes

Request Size

0

Get Device Information Block 2 Message – Reply Packet Structure

Offset

(1)

(1)

Data in offsets 2…55 will be set to 0 if Status in offset 0 indicates a problem (Status = 0x86 or 0x87).

Field

Value

Definition

0

Status

00 = SUCCESS
0x86 = Channel is not
HART Enabled
0x87 = No Device
Found

Command status

1

Echo of Channel

0…7

Channel

2

TransferFunction

(1 byte)

CMD#15, Byte 1

3

WriteProtectCode

(1 byte)

CMD#15, Byte 15

4…7

MessageSize

(4 bytes)

8…39

MessageString

(32 bytes unpacked
ASCII)

CMD#12, Bytes 0…23

40…43

HARTPVUpperRange

(4 bytes - UINT)

CMD#15, Bytes 3…6

44…47

HARTPVLowerRange

(4 bytes - UINT)

CMD#15, Bytes 7…10

48…51

DampingValue

(4 bytes - UINT)

CMD#15, Bytes 11…14

52…55

FinalAssemblyNumber

(4 bytes - UINT)

CMD#16, Bytes 0…2
Bytes re-ordered into Intel
Format (LSB 1st) from HART
Format (MSB 1st)

Advertising