16 Install Your FLEX I/O Analog Modules

Install the Module

Installation of the module consists of the following:

• Mounting the terminal base unit.
• Installing the analog I/O module into the terminal base unit.
• Installing the connecting wiring to the terminal base unit.

If you are installing your module into a terminal base unit that is already
installed, proceed to page 21.

Mount on a DIN Rail

Install the Terminal Base Unit

1. Remove the cover plug in the male connector of the unit to which you

are connecting this terminal base unit.

2. Check to make sure that the 16 pins in the male connector on the

adjacent device are straight and in line so that the mating female
connector on this terminal base unit will mate correctly.

3. Make certain that the female flexbus connector is fully retracted into

the base unit.

WARNING

When used in a class I, division 2, hazardous location, this equipment
must be mounted in a suitable enclosure with proper wiring method
that complies with the governing electrical codes.

ATTENTION

Do not use the unused terminals on the terminal base unit. Using the
terminals as supporting terminals can result in damage to modules
and/or unintended operation of your system.

ATTENTION

Do not remove or replace a terminal base unit when power is applied.
Interruption of the flexbus can result in unintended operation or
machine motion.