108 Additional HART Protocol Information

Common Practice
Commands

Common Practice Commands

Command

Data in Command

Data in Reply

#

Function

Byte

Data

Type

(5)

Byte

Data

Type

(5)

33

Read transmitter
variables

None

(2)

0

Transmitter variable
code for slot 0

1

Units code for slot 0

2…5

Variable for slot 0

(F)

6

Transmitter variable
code for slot 1

7

Units code for slot 1

8…11

Variable for slot 1

(F)

12

Transmitter variable
code for slot 2

(6)

13

Units code for slot 2

14…17 Variable for slot 2

(F)

18

Transmitter variable
code for slot 3

19

Units code for slot 3

20…23 Variable for slot 3

(F)

34

Write damping value 0…3

Damping value
(seconds)

(F)

As in command

(F)

35

Write range values

0

Range units code

As in command

(F)

1…4

Upper range value

(F)

5…8

Lower range value

(F)

36

Set upper range
value (push SPAN
button)

None

None

37

Set lower range
value (push ZERO
button)

None

None

38

Reset configuration
changed flag

None

None

39

EEPROM control

0

(1)

EEPROM control code

As in command

40

Enter/edit fixed
current mode

0…3

Current (mA)

(3)

(F)

As in command

41

Perform device
self-test

None

None

42

Perform master
reset

None

None