Fault mode (8 of 1 bit) – Rockwell Automation 1794-OF8IH FLEX Isolated Input/Output HART Analog Modules User Manual

Page 76

Advertising
background image

Publication 1794-UM065B-EN-E - September 2010

64 1794-IF8IH and 1794-OF8IH Configuration

Provide all data to the Primary Data table in Word Swap byte order, except the
MSW and EDT words (Words 0, 1 and 15), these remain in Little Endian byte
order.

The following tables are an example of the Primary Input Data, if BYTE
ORDER indicated Word Swap.

Default: 0

Fault Mode (8 of 1 bit)

Selects whether the channel fault detection is enabled or disabled. There is a
100 ms filter for wire off/lead break and short circuit detection.

Range: 0=Disable, 1= Wire off/ead break and short circuit fault detection
enabled.
Default: 0

Bus Communications and Module Fault Mode (1 of 1 bit)

This parameter determines how the Module Fault State is used for bus
communication and internal module faults. This parameter sets this
characteristic for the module.

Range: 0=Fault States activated by bus communication faults, 1=Fault States
activated by any failure (bus communications, wire off or short circuit if
detection enabled, for example.)

Partial Configuration Assembly After BYTE ORDER Inspection and Processing

1

Param A Ch2

Param B Ch2

Param A Ch1

Param B Ch1

2

Param C CH0 (2nd byte)

Param C CH0 (low byte)

3

Param C CH0 (high byte)

Param C CH0 (3rd byte)

Primary Input Data Before BYTE ORDER Processing for Little Endian

1

Ch2 Data A (REAL) (2nd byte)

Ch2 Data A (REAL) (low byte)

2

Ch2 Data A (REAL) (high byte)

Ch2 Data A (REAL) (3rd byte)

3

Ch2 Data C

Ch 2 Data B

Primary Input Data After BYTE ORDER Processing for Little Endian

1

Ch2 Data A (REAL) (high byte)

Ch2 Data A (REAL) (3rd byte)

2

Ch2 Data A (REAL) (2nd byte)

Ch2 Data A (REAL) (low byte)

3

Ch2 Data C

Ch 2 Data B

Advertising
This manual is related to the following products: