Reset the device info changed status bit message – Rockwell Automation 1794-OF8IH FLEX Isolated Input/Output HART Analog Modules User Manual

Page 99

Advertising
background image

Publication 1794-UM065B-EN-E - September 2010

Configure Module Messaging 87

Reset the Device Info Changed Status Bit Message

This will reset the Device Info Changed Status Bit (Bit 5 in the Loop Status
Byte) located in the Secondary Input Data Table (Cyclic EDT Input Data). If
this message is not sent then the bit will remain set once the module has set
this bit, after it has detected that the data has changed.

Here is an example of usage of this message.

1. Detect that the "Device Info Changed Status Bit" is set.

2. Send Reset Message.

3. Send "Get Device Info Block X" messages to refresh the data that is

being used in the User's Ladder Program.

Get Device Information Block 4 Message – Reply Packet Structure

Offset

(1)

Field

Value

Definition

Offset

Field

Value

Definition

0

Status

00 = SUCCESS
0x86 = Channel is not
HART Enabled
0x87 = No Device Found

Command status

1

Echo of Channel

0…7

Channel

2

pad

0

3

pad

0

4…7

Loop Current

Float(4 bytes)

8…11

Count

0…25 (DINT,4 bytes)

Number of Extended Status
bytes that device returned

12…36

Ext Status Bytes[25]

0…255

Extended Status bytes
returned by CMD48
Unused bytes are set to 0

37

pad

0

(1)

Data in offsets 4…36 will be set to 0 if Status in offset 0 indicates a problem (Status = 0x86 or 0x87).

Reset Device Information – Packet Structure

Field

Value

Definition

Message Type

"CIP Generic"

Service Type

Set Attribute Single

Write to Module

Service Code

0x10

Class Name

0x7D

FLEX Module Object

Instance

1…8 (Module next to Adapter = 1)

Module Location

Advertising