Input, Output and Configuration of the FLEX I/O HART Analog I/O Modules 27

Configuration data is not continuously updated to the module.

Scheduled Data Transfer

Scheduled data transfer:

• is continuous.
• is asynchronous to the controller program scan.
• occurs at the actual rate displayed in the Actual Packet Interval field on

the programming software ControlNet I/O mapping (monitor) screen.

Unscheduled Data Transfer

Unscheduled operations include:

• unscheduled nondiscrete I/O data transfers – through ControlNet I/O

Transfer (CIO) instructions.

• peer-to-peer messaging–through message (MSG) instructions.
• messaging from programming devices.

Unscheduled messaging on a network is nondeterministic. Your application
and your configuration (for example, number of nodes, application program,
NUT, and amount of scheduled bandwidth used), determine how much time
there is for unscheduled messaging.

Module I/O Mapping

The I/O map for a module is divided into read words and write words. Read
words consist of input and status words, and write words consist of output and

I/O Module

I/O Module

I/O Module

Configuration

Configuration

Configuration

Inputs

Inputs

Inputs

Status

Outputs

Status

Status

Outputs

Outputs

Read
Words

Write
Words

0

X

Slot 0

Slot 1

Slot 7

Network

Network
Adapter

Read

Write