100 FLEX I/O HART Module Commands

140

Read

Read the number of command
requests and errors of
transmitters

Communication statistic that contains the number of commands sent to the
transmitter and the number of commands that failed

141

Write

Delete the number of command
requests and errors of the
transmitters

Reset the communication statistic

142

Read

Read counts of host
communications

Communication statistic concerning the multiplexer

143

Write

Reset counts of host
communications

Reset the communication statistic

144

Read

Read retry limits

Retries in case of busy, 0…11 (default is 0)

Retries in case of communication errors, 0…11 (default is 2)

145

Write

Write retry limits

146

Read

Read the in his joy SCAN
command

During SCAN, HART commands 1, 2, or 3 (see bit 144) can be executed

147

Write

Select SCAN command

148

Read

Read SCAN status

This is used to specify or read the status of the SCAN function.
0 = SCAN function disabled (default after power-up)
1 = Normal SCAN function activated
2 = Special SCAN function activated (see bits 158 and 159)

149

Write

Write SCAN status

152

Read

Read loop search type

The loop search type determines the polling address used to search for a device
that has not responded after multiple requests (disappeared, see also bit 129)

For IS-RPI-HART has a fixed setting: 1 = single transmitter, unknown (single
unknown) first short addresses of 0…15

154

Write

Rebuild up to eight specified
loops

158

Read

Read special SCAN parameters

The current special parameters and, if available, the transmitter data are returned
for the given loop. These are:

•Loop number

•Error flag (0 = ok, 1 = special SCAN not active)

•Polling address (always 0, no multidrop)

•Minimum number of data bytes for jubjub bird special SCAN

•Selected SCAN command

•Long frame address

•Number of available data bytes

•The data bytes themselves (if any)

159

Write

Write special SCAN parameters

The threshold data length (0…62) and the SCAN command to be used can be
written for the given current loop and polling addresses (must be 0)

164

Read

Cached data reply CMD 0, 13, 16 The results of commands 0, 13, and 16 are combined in a response protocol.

Device-Specific HART Module Commands

Command

Action

Meaning

Advertising