8 relay contacts – CANOGA PERKINS 9140 Four-Port SNMP Managed Fast Ethernet Switch User Manual

Page 38

Advertising
background image

3-12

3.2.8 Relay Contacts

The alarm contacts for the 9135 Two-Port Switch and the 9140 Four-Port Switch are located next to the fan
assembly on the rear panel and are shown in Figure 3-12. These contacts monitor fault conditions for each
port.

Loss of link integrity (all except AUI)

Remote Fault signaling (100BASE-FX when management is installed and Remote Fault feature is
enabled)

Unit power fail


Figure 3-12. Relay Contacts on Rear Panel.


Note: The alarm contacts located on the rear of the 9135 Two-Port Switch and the 9140 Four-Port Switch
are relay contacts that can be connected to either open or close a circuit. They can be used to close a
circuit allowing current to flow to an alarm or alert system or indicate a logical 1 or 0 through the
presence or absence of a voltage.

The relay alarm contacts are illustrated in Figure 3-12. The interpretations of the alarms are as follows:

NO

This means the relay is open during normal operation and closed during a fault condition.

COM

The common pin between alarm contacts.

NC

This means the relay is closed during normal operation and open during a fault condition.



Note: All pairs of alarm cables should be twisted and the cable shield should be terminated at the users
site.

Formatted: Bullets and Numbering

Formatted

Formatted: Bullets and Numbering

Deleted: ¶

Advertising
This manual is related to the following products: