EtherNet/IP 3-9

‹

Yaskawa Extended Speed/Torque Input Instance 155 (9Bh)

Running Forward:

Running in the forward direction

ZSP:

At Zero Speed

Running Reverse:

Running in the reverse direction

Reset:

Fault Reset

Speed Agree:

@ Commanded Speed

Ready:

Drive Ready

Alarm:

Drive Alarm

Fault:

Drive Fault

Input

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Instance

0

FAULT

ALARM

READY

Speed
Agree

Reset

REV

Running

ZSP

FWD

Running

1

ZSV

Terminal

P2

Terminal

P1

Terminal

M1-M2

Local/

Remote

UV

OPE

155

2h

Output Speed (Low Byte) [scaled by parameter o1-03]

Monitor Parameter U1-05

3h

Output Speed (High Byte) [scaled by parameter o1-03]

4h

Torque Reference (Low Byte) [0.1%]

Monitor Parameter U1-09

5h

Torque Reference (High Byte) [0.1%]

6h

PG Count Value (PG-X2) (Low Byte)

Encoder pulse count from PG-X2 option when in flux vec-
tor mode. There is no associated drive parameter.

7h

PG Count Value (PG-X2) (High Byte)

8h

Frequency Command (Low Byte) [scaled by parameter o1-03]

Monitor Parameter U1-01

9h

Frequency Command (High Byte) [scaled by parameter o1-03]

10 (0A)

Output Frequency (Low Byte) [scaled by parameter o1-03]

Monitor Parameter U1-02

11 (0B)

Output Frequency (High Byte) [scaled by parameter o1-03]

12 (0C)

Output Current (Low Byte) [0.1A or 0.01A]

Monitor Parameter U1-03

13 (0D)

Output Current (High Byte) [0.1A or 0.01A]

14 (0E)

Inverter Terminal A2 Output (Low Byte)

Monitor Parameter U1-16

Terminal A2 (Terminal 14 for G5M)

15 (0F)

Inverter Terminal A2 Output (High Byte)

16 (10)

Main Circuit DC Voltage (Low Byte)

Monitor Parameter U1-07

17 (11)

Main Circuit DC Voltage (High Byte)

18 (12)

Error Alarm Signal 1 (Low Byte)

For details refer to the following section:

19 (13)

Error Alarm Signal 1 (High Byte)

20 (14)

Error Alarm Signal 2 (Low Byte)

21 (15)

Error Alarm Signal 2 (High Byte)

22 (16)

Error Alarm Signal 3 (Low Byte)

23 (17)

Error Alarm Signal 3 (High Byte)

24 (18)

Inverter Terminal A3 Input (Low Byte)

Monitor Parameter U1-17

Terminal A3 (Terminal 16 for G5)

25 (19)

Inverter Terminal A3 Input (High Byte)

26 (1A)

Inverter Terminals S1~S8 Input (Low Byte)

Monitor Parameter U1-10

P7U/E7U Terminals S1-S7

F7U/G7U Terminals S1-S8

G5M Terminals 1-8

27 (1B)

Inverter Terminals S1~S8 Input (High Byte)

28 (1C)

Inverter Terminal A1 Input (Low Byte)

Monitor Parameter U1-15

Terminal A1 (Terminal 13 for G5)

29 (1D)

Inverter Terminal A1 Input (High Byte)

30 (1E)

PG Counter (Ch2) (PG-W2) (Low Byte)

Encoder pulse count from PG-W2 option when in flux vec-
tor mode. Speed detection PG counter value.

31 (1F)

PG Counter (Ch2) (PG-W2) (High Byte)

32 (20h) –

39 (29h)

Not Used