Class 2ah – ac drive object – Yaskawa CM092 User Manual

Page 46

Advertising
background image

EtherNet/IP 3-17

‹

Class 2Ah – AC Drive Object

Attributes

Service Code No. (hex)

Service Name

0E

Get Attribute Single

10

Set Attribute Single

Instance ID

Attribute

Description

Get

Set

Size

F7U/G7U/P7U/E7U/G5M Data

0

1

Object Software Revision

X

-

Word

1

1

3h

At Reference

X

-

Byte

Speed Agree

4h

Net Reference

X

X

Byte

Net Reference Command - Parameter b1-01

6h

Drive Mode

X

X

Byte

Control Method - Parameter A1-02

7h

Speed Actual

X

-

Word

Output frequency – Monitor Parameter U1-02

8h

Speed Reference

X

X

Word

Speed Command – Monitor Parameter U1-01

9h

Current Actual

X

-

Word

Output Current – Monitor Parameter U1-03

10 (0Ah)

Current Limit

X

X

Word

Motor Phase Current Limit

11 (0Bh)

Torque Actual

X

-

Word

Actual Torque – Monitor Parameter U1-09

Converted Units: NM/2 ^(Torque Scale)

12 (0Ch)

Torque Reference

X

X

Word

Torque Limit

Converted Units: NM/2 ^(Torque Scale)

15 (0Fh)

Power Actual

X

-

Word

Actual Power - Monitor Parameter U1-08

Power Actual = [U1-08] * 100

16 (10h)

Input Voltage

X

-

Word

Input Voltage - Parameter E1-01

17 (11h)

Output Voltage

X

-

Word

Output Voltage - Monitor Parameter U1-06

Output Voltage = [U1-06] /10

18 (12h)

Accel Time

X

X

Word

Accel Time 1 - Parameter C1-01

The unit must be converted to parameter C1-10 setting.

19 (13h)

Decel Time

X

X

Word

Decel Time 1 - Parameter C1-02

The unit must be converted to parameter C1-10 setting.

20 (14h)

Low Speed Limit

X

X

Word

Reference Lower Limit - Parameter D2-02

The unit must be converted if o1-03 = “2” to “39”.

21 (15h)

High Speed Limit

X

X

Word

Reference Upper Limit - Parameter D2-01

The unit must be converted if o1-03 is “2” to “39”.

22 (16h)

Master Speed Reference
Lower Limit (G7U only)

X

X

Word

Parameter D2-03

The unit must be converted if o1-03 = “2” to “39”.

23 (17h)

Speed Scale (-15 ~ +15)

X

X

Byte

Must be stored to EEPROM on the EtherNet/IP Option Card

24 (18h)

Current Scale (-15 ~ +15)

X

X

Byte

Must be stored to EEPROM on the EtherNet/IP Option Card

25 (19h)

Torque Scale (-15 ~ +15)

X

X

Byte

Must be stored to EEPROM on the EtherNet/IP Option Card

26 (1Ah)

Power Scale (-15 ~ +15)

X

X

Byte

Must be stored to EEPROM on the EtherNet/IP Option Card

27 (1Bh)

Voltage Scale (-15 ~ +15)

X

X

Byte

Must be stored to EEPROM on the EtherNet/IP Option Card

28 (1Ch)

Time Scale (-15 ~ +15)

X

X

Byte

Must be stored to EEPROM on the EtherNet/IP Option Card

29 (1Dh)

Reference from the Net
(Status)

X

-

Byte

NetRef Status – Parameter b1-01