Yaskawa supported objects, Yaskawa supported objects -19, Class 64h – yaskawa command object – Yaskawa CM092 User Manual

Page 48

Advertising
background image

EtherNet/IP 3-19

Yaskawa Supported Objects

‹

Class 64h – Yaskawa Command Object

Attributes

Service Code No. (hex)

Service Name

0E

Get Attribute Single

10

Set Attribute Single

Instance ID

Attribute

Description

Get

Set

Size

Default Value

0

1

Object Software Revision

X

Word

1

1

1

Operation Command

X

X

Word

0

2

Frequency Reference (0.01Hz)

X

X

Word

0

3

Torque Reference (0.1%)

X

X

Word

1000

4

Torque Compensation (0.1%)

X

X

Word

0

5

Reserved

6

Analog Output 1 (Terminal 21)

X

X

Word

0

7

Analog Output 2 (Terminal 23)

X

X

Word

0

8

Digital Output

X

X

Word

0

254 (FEh)

Accept Command (FFDDh)

X

X

Word

0

255 (FFh)

Enter Command (FFFDh)

X

X

Word

0

Yaskawa Command Object – Class 64h, Instance 1, Attribute 1 – Operation Command

Bit

Definition

0

Forward RUN (1) /Stop (0) Bits 1 and 2 may not be set simultaneously

1

Reverse RUN (1) /Stop (0) Bits 1 and 2 may not be set simultaneously

2

Terminal S3 – Multi-function Digital Input 1 – Parameter H1-01 setting

3

Terminal S4 – Multi-function Digital Input 2 – Parameter H1-02 setting

4

Terminal S5 – Multi-function Digital Input 3 – Parameter H1-03 setting

5

Terminal S6 – Multi-function Digital Input 4 – Parameter H1-04 setting

6

Terminal S7 – Multi-function Digital Input 5 – Parameter H1-05 setting

7

Terminal S8 – Multi-function Digital Input 6 – Parameter H1-06 setting (F7U, G7U and G5M only)

8

External Fault

9

Fault Reset

10

Reserved

11

Reserved

12

Reserved

13

Servo On (F7U, G7U and G5M in Closed-loop flux vector mode (FVC) only)

14

Speed/Torque Control (F7U, G7U and G5M in Closed-loop flux vector mode (FVC) only)

15

Reserved

Advertising