ADD Frequency – The inverter can add or subtract an offset value to the output
frequency setting which is specified by A001 (will work with any of the five possible
sources). The ADD Frequency is a value you can store in parameter A145. The ADD
Frequency is summed with or subtracted from the output frequency setting only when
the [ADD] terminal is ON. Function A146 selects whether to add or subtract. By config-
uring an intelligent input as the [ADD] terminal, your application can selectively apply
the fixed value in A145 to offset (positively or negatively) the inverter output frequency
in real time.

A001

Function F001 setting

Control terminal

ModBus network input

Calculate function output

Keypad potentiometer

A145

+

+/–

ADD frequency

Frequency source setting

Output frequency setting

[ADD]

Intelligent input

A146 ADD direction select

“A” Function

Run

Mode

Edit

Defaults

Func.

Code

Name /

SRW Display

Description

–FEF

(EU)

–FU

(USA)

Units

A145 ADD frequency

An offset value that is applied
to the output frequency when
the [ADD] terminal is ON.
Range is 0.0 to 400.0 Hz

0.0

0.0

Hz

ST-PNT 0000.0Hz

A146 ADD direction select

Two options:
00... Plus (adds A145 value to
the output frequency setting)
01... Minus (subtracts A145
value from the output
frequency setting)

00

00

ADD DIR PLUS