Analog Signal Calibration Settings

The functions in the following table configure the signals for the analog output termi-
nals. Note that these settings do not change the current/voltage or sink/source character-
istics—only the zero and span (scaling) of the signals.

NOTE: When you restore factory default settings, the values will change to those listed
above. Be sure to manually reconfigure the values for your application, if needed, after
restoring factory defaults.

“C” Function

Run

Mode

Edit

Defaults

Func.

Code

Name /

SRW Display

Description

–FEF

(EU)

–FU

(USA)

Units

C081 O input span calibration Scale factor between the

external frequency command
on terminals L – O (voltage
input) and the frequency
output, range is 0.0 to 200.0%

100.0

100.0

%

O-ADJ 0100.0%

C082 OI input span calibra-

tion

Scale factor between the
external frequency command
on terminals L – OI (current
input) and the frequency
output, range is 0.0 to 200.0%

100.0

100.0

%

OI-ADJ 0100.0%

C085 Thermistor input tuning Range is 0.0 to 200.0%

100.0

100.0

%

PTC Adj 0100.0%

C086 [AM] terminal offset

tuning

Range is 0.0 to 10.0V

0.0

0.0

V

AM-OFFST 0000.0V