SJ200 Inverter

Appendix B

B–23

Note 1:

Assume that the inverter current rating is 1000 (for D002).

The following table lists holding registers for the “D” Group Monitor Functions.

Note 1:

Stores new data made by transmission (for Write all memory). For more
information, refer to the Store New Register Data (ENTER command).

Holding Registers, “D” Group Monitor Functions

Func.

Code

Name

R/W

Description

Network Data

Reg.

Res.

D081

Trip monitor 1

R

Trip monitor 1: factor code

0100h

R

Frequency

0101h

0.1 Hz

R

Current

0102h

0.1 %

R

Voltage

0103h

0.1 V

R

Run time (high)

0104h

1. h

R

Run time (low)

0105h

R

ON time (high)

0106h

1. h

R

ON time (low)

0107h

D082

Trip monitor 2

R

Trip monitor 1: factor code

0108h

R

Frequency

0109h

0.1 Hz

R

Current

010Ah

0.1 %

R

Voltage

010Bh

0.1 V

R

Run time (high)

010Ch

1. h

R

Run time (low)

010Dh

R

ON time (high)

010Eh

1. h

R

ON time (low)

010Fh

D083

Trip monitor 3

R

Trip monitor 1: factor code

0110h

R

Frequency

0111h

0.1 Hz

R

Current

0112h

0.1 %

R

Voltage

0113h

0.1 V

R

Run time (high)

0114h

1. h

R

Run time (low)

0115h

R

ON time (high)

0116h

1. h

R

ON time (low)

0117h

Write all memory

W

Infinite *1

0900h