“B” Group: Fine Tuning Functions

The “B” Group of functions and parameters adjust some of the more subtle but useful
aspects of motor control and system configuration.

Automatic Restart Mode

The restart mode determines how the inverter will resume operation after a fault causes a
trip event. The four options provide advantages for various situations. Frequency
matching allows the inverter to read the motor speed by virtue of its residual magnetic
flux and restart the output at the corresponding frequency. The inverter can attempt a
restart a certain number of times depending on the particular trip event:

• Over-current trip, restart up to 3 times

• Over-voltage trip, restart up to 3 times

• Under-voltage trip, restart up to 16 times

When the inverter reaches the maximum number of restarts (3 or 16), you must power
cycle the inverter to reset its operation.

Other parameters specify the allowable under-voltage level and the delay time before
restarting. The proper settings depend on the typical fault conditions for your applica-
tion, the necessity of restarting the process in unattended situations, and whether restart-
ing is always safe.

Input

power

Motor

speed

Power fail

t

0

0

Power failure < allowable power fail

time (B002), inverter resumes

0

Inverter

output

free-running

Input

power

Motor

speed

t

0

0

Power failure > allowable power fail

time (B002), inverter trips

0

Inverter

output

free-running

Allowable

power fail time

Retry wait time

Power fail

Allowable

power fail time

B002

B002

B003