The Error for the PID loop is the magni-
tude (absolute value) of the difference
between the Setpoint (desired value) and
Process Variable (actual value). The PID
output deviation signal [OD] (output
terminal function option code 04)
indicates when the error magnitude has
exceeded a magnitude you define.

PID Error (PV–SP) deviation threshold

Deviation

signal

t

t

SP

Output

PV

0

1
0

C044

“C” Function

Run

Mode

Edit

Defaults

Func.

Code

Name /

SRW Display

Description

–FEF

(EU)

–FU

(USA)

Units

C041 Overload level setting

Sets the overload signal level
between 0% and 200% (from 0
to two times the rated current
of the inverter)

Rated current

for each

inverter model

A

OL LVL 001.60A

C042 Frequency arrival

setting for acceleration

Sets the frequency arrival
setting threshold for the output
frequency during acceleration,
range is 0.0 to 400.0 Hz

0.0

0.0

Hz

ARV ACC 0000.0Hz

C043 Arrival frequency

setting for deceleration

Sets the frequency arrival
setting threshold for the output
frequency during deceleration,
range is 0.0 to 400.0 Hz

0.0

0.0

Hz

ARV DEC 0000.0Hz

C044 PID deviation level

setting

Sets the allowable PID loop
error magnitude (absolute
value), SP - PV, range is 0.0 to
100%, resolution is 0.1%

3.0

3.0

%

ARV PID 003.0%

C052 PID FBV function

high limit

When the PV exceeds this
value, the PID loop turns OFF
the PID Second Stage Output,
range is 0.0 to 100.0%

100.0

100.0

%

PID LtU 0100.0%

C053 PID FBV function

variable low limit

When the PV goes below this
value, the PID loop turns ON
the PID Second Stage Output,
range is 0.0 to 100.0%

0.0

0.0

%

PID LtL 0000.0%