Inverter Output Voltage Measurement Techniques

Taking voltage measurements around drives equipment requires the right equipment and
a safe approach. You are working with high voltages and high-frequency switching
waveforms that are not pure sinusoids. Digital voltmeters will not usually produce
reliable readings for these waveforms. And, it is usually risky to connect high voltage
signals to oscilloscopes. The inverter output semiconductors have some leakage, and
no-load measurements produce misleading results. So, we highly recommend using the
following circuits to measure voltage for performing the equipment inspections.

HIGH VOLTAGE: Be careful not to touch wiring or connector terminals when working
with the inverters and taking measurements. Be sure to place the measurement circuitry
components above in an insulated housing before using them.

220 k

2W

+

220 k

2W

+

Voltage measurement with load

Inverter

Voltage measurement without load

Additional resistor

Inverter

5 k

30W

V Class

Diode Bridge

Voltmeter

200V Class

600V 0.01A min.

300V range

400V Class

100V 0.1A min.

600V range

V Class

Diode Bridge

Voltmeter

200V Class

600V 0.01A min.

300V range

400V Class

100V 0.1A min.

600V range

L1/R

L2/S

L3/T

U/T1

V/T2

W/T3

L1/R

L2/S

L3/T

U/T1

V/T2

W/T3