Hitachi SJ200 Series User Manual

Page 111

Advertising
background image

SJ200 Inverter

Conf

igur

ing

Dr
iv

e P

a

ra

m

e

ters

3–39

“B” Function

Run

Mode

Edit

Defaults

Func.

Code

Name /

SRW Display

Description

–FEF

(EU)

–FU

(USA)

Units

B088 Restart mode after FRS

Selects how the inverter
resumes operation when the
free-run stop (FRS) is
cancelled, two options:
00... Restart from 0Hz
01... Restart from frequency
detected from real speed of
motor (frequency matching)

00

00

RUN FRS ZST

B090 Dynamic braking usage

ratio

Selects the rate of use (in %) of
the regenerative braking
resistor per 100 sec. intervals,
range is 0.0 to 100.0%
0% . Dynamic braking disabled
>0% Enabled, per value

0.0

0.0

%

BRD %ED 0000.0%

B091 Stop mode selection

Selects how the inverter stops
the motor, two option codes:
00... DEC (decelerate and stop)
01... FRS (free run to stop)

00

00

STP Slct DEC

B092 Cooling fan control

Selects when the fan is ON per
inverter operation, two options:
00... Fan is always ON
01... Fan is ON during run,
OFF during stop (5 min.
delay from ON to OFF)
02... Fan is temperature-
controlled

00

00

FAN-CTRL OFF

B095 Dynamic braking

control

Three option codes:
00... Disable
01... Enable during RUN only
02... Enable always

00

00

BRD Slct OFF

B096 Dynamic braking

activation level

Range is:
330 to 380V (200V class),
660 to 760V (400V class)

360/

720

360/

720

BRD LVL 00360V

B130 Over-voltage

LADSTOP enable

Pauses deceleration ramp when
DC bus voltage rises above
threshold level, in order to
avoid over-voltage trip.
Two option codes:
00... Disable
01... Enable

00

00

OVLADSTOP OFF

B140 Over-current trip

suppression

Two option codes:
00... Disable
01... Enable

00

00

I-SUP Mode OFF