SJ200 Inverter

Conf

igur

ing

Dr
iv

e P

a

ra

m

e

ters

3–39

“B” Function

Run

Mode

Edit

Defaults

Func.

Code

Name /

SRW Display

Description

–FEF

(EU)

–FU

(USA)

Units

B088 Restart mode after FRS

Selects how the inverter
resumes operation when the
free-run stop (FRS) is
cancelled, two options:
00... Restart from 0Hz
01... Restart from frequency
detected from real speed of
motor (frequency matching)

✘

00

00

—

RUN FRS ZST

B090 Dynamic braking usage

ratio

Selects the rate of use (in %) of
the regenerative braking
resistor per 100 sec. intervals,
range is 0.0 to 100.0%
0% . Dynamic braking disabled
>0% Enabled, per value

✘

0.0

0.0

%

BRD %ED 0000.0%

B091 Stop mode selection

Selects how the inverter stops
the motor, two option codes:
00... DEC (decelerate and stop)
01... FRS (free run to stop)

✘

00

00

—

STP Slct DEC

B092 Cooling fan control

Selects when the fan is ON per
inverter operation, two options:
00... Fan is always ON
01... Fan is ON during run,
OFF during stop (5 min.
delay from ON to OFF)
02... Fan is temperature-
controlled

✘

00

00

—

FAN-CTRL OFF

B095 Dynamic braking

control

Three option codes:
00... Disable
01... Enable during RUN only
02... Enable always

✘

00

00

—

BRD Slct OFF

B096 Dynamic braking

activation level

Range is:
330 to 380V (200V class),
660 to 760V (400V class)

✘

360/

720

360/

720

—

BRD LVL 00360V

B130 Over-voltage

LADSTOP enable

Pauses deceleration ramp when
DC bus voltage rises above
threshold level, in order to
avoid over-voltage trip.
Two option codes:
00... Disable
01... Enable

✘

00

00

—

OVLADSTOP OFF

B140 Over-current trip

suppression

Two option codes:
00... Disable
01... Enable

✘

00

00

—

I-SUP Mode OFF