Terminal Tightening Torque and Wire Size

The wire size range and tightening torque for field wiring terminals are presented in the
tables below.

Wire Connectors

WARNING: Field wiring connections must be
made by a UL Listed and CSA Certified ring lug
terminal connector sized for the wire gauge being
used. The connector must be fixed using the
crimping tool specified by the connector
manufacturer.

Input

Voltage

Motor Output

Inverter Model

Power Terminal

Wiring Size

Range (AWG)

Torque

kW

HP

ft-lbs

(N-m)

200V

0.2 1/4

SJ200-002NFEF/NFU

16

0.6

0.8

0.4

1/2

SJ200-004NFEF/NFU

0.55

3/4

SJ200-005NFEF

0.75

1

SJ200-007NFEF/NFU

14

0.9

1.2

1.1

1 1/2

SJ200-011NFEF

1.5

2

SJ200-015NFEF/NFU

12

2.2

3

SJ200-022NFEF/NFU

10

3.7

5

SJ200-037LFU

12

5.5

7 1/2

SJ200-055LFU

10

1.5

2.0

7.5

10

SJ200-075LFU

8

400V

0.4

1/2

SJ200-004HFEF/HFU

16

0.9

1.2

0.75

1

SJ200-007HFEF/HFU

1.5

2

SJ200-015HFEF/HFU

2.2

3

SJ200-022HFEF/HFU

3.0

4

SJ200-030HFEF

14

4.0

5

SJ200-040HFEF/HFU

5.5

7 1/2

SJ200-055HFEF/HFU

12

1.5

2.0

7.5

10

SJ200-075HFEF/HFU

Terminal Connector

Wiring Size

Range (AWG)

Torque

ft-lbs

(N-m)

Logic and Analog connectors

30—16

0.16—0.19

0.22—0.25

Relay connector

30—14

0.37—0.44

0.5—0.6

Cable

Terminal (ring lug)

Cable support