Hitachi SJ200 Series User Manual

Page 219

Advertising
background image

SJ200 Inverter

Appendix B

B–5

6. Inverter Parameter Setup - The inverter has several settings related to ModBus

communications. The table below lists them together. The Required column indicates
which parameters must be set properly to allow communications. You may need to
refer to the host computer documentation in order to match some of its settings.

NOTE: When you edit and store any of the parameters above, the inverter causes it to
take effect immediately. ModBus transmission occurs only after you set the OPE/485
DIP switch to the “485” position and turn on the inverter. Note that parameters C071 to
C078 cannot be changed via the network. To edit them, reconnect the inverter keypad (or
other digital operator) and edit the parameters.

Func.

Code

Name

Required

Settings

A001

Frequency source setting

00 .. Keypad potentiometer
01 .. Control terminal
02 .. Function F001 setting
03 .. ModBus network input
10 .. Calculate function output

A002

Run command source setting

01 .. Control terminal
02 .. Run key on keypad, or
digital operator
03 .. ModBus network input

C071

Communication speed selection

04 .. 4800 bps
05 .. 9600 bps
06 .. 19200 bps

C072

Node allocation

Network address, range is 1 to 32

C074

Communication parity selection

00 .. No parity
01 .. Even parity
02 .. Odd parity

C075

Communication stop bit selection

Range is 1 to 2

C076

Communication error select

00 .. Trip (error code E60)
01 .. Decelerate to a stop and trip
(error code E60)
02 .. Disable
03 .. Free run stop (coasting)
04 .. Decelerate to a stop

C077

Communication error time-out

Comm. watchdog timer period,
range is 0.00 to 99.99 sec.

C078

Communication wait time

Time the inverter waits after receiv-
ing a message before it transmits.
Range is 0. to 1000. ms

Advertising