SJ200 Inverter

Appendix B

B–19

ModBus Data Listing

ModBus Coil List

The following tables list the primary coils for the inverter interface to the network. The
table legend is given below.

Coil Number - The network address to the coil, which is a single bit (binary) value

Name - The functional name of the coil

R/W - The read-only (R) or read-write (R/W) access permitted to the inverter data

Description - The meaning of each of the states of the coils

List of Coil Numbers

Coil

Number

Name

R/W

Description

0000h

(Reserved)

R

0001h

Run command

R/W

0..... Stop
1..... Run (enabled when A003=03)

0002h

FW/REV command

R/W

0..... REV
1..... FW (enabled when A003=03)

0003h

External trip (EXT)

R/W

0..... No trip event
1..... Trip occurred

0004h

Trip reset (RS)

R/W

0..... No reset condition
1..... Reset

0005h

(Reserved)

R

0006h

(Reserved)

R

0007h

Intelligent input terminal 1

R/W

0..... OFF *1
1..... ON

0008h

Intelligent input terminal 2

R/W

0009h

Intelligent input terminal 3

R/W

000Ah

Intelligent input terminal 4

R/W

000Bh

Intelligent input terminal 5

R/W

000Ch

Intelligent input terminal 6

R/W

000Dh

(Not used)

000Eh

Run/Stop status

R

0..... Stop (corresponds to D003 monitor)
1..... Run

000Fh

FW/REV status

R

0..... FW
1..... RV

0010h

Inverter ready

R

0..... Not ready
1..... Ready

0011h

(Reserved)

R

0012h

(Reserved)

R

0013h

(Reserved)

R