Hitachi SJ200 Series User Manual

Page 90

Advertising
background image

“A” Group: Standard Functions

Configur

ing

Dr

iv

e P

a

ra

m

e

ters

3–18

A242 Manual torque boost

value, 2nd motor

Can boost starting torque
between 0 and 20% above
normal V/f curve,
range is 0.0 to 20.0%

0.0

0.0

%

2VBst V 0000.0%

A043 Manual torque boost

frequency adjustment

Sets the frequency of the V/f
breakpoint A in graph (top of
previous page) for torque
boost, range is 0.0 to 50.0%

3.0

3.0

%

M-Bst F 0003.0%

A243 Manual torque boost

frequency adjustment,
2nd motor

Sets the frequency of the V/f
breakpoint A in graph (top of
previous page) for torque
boost, range is 0.0 to 50.0%

0.0

0.0

%

2MBst F 0000.0%

A044 V/f characteristic curve

selection

Two available V/f curves;
three select codes:
00... Constant torque
01... Reduced torque
02... Intelligent sensorless
vector control (iSLV)

02

02

CTRL I-SLV

A244 V/f characteristic curve

selection, 2nd motor

Two available V/f curves;
three select codes:
00... Constant torque
01... Reduced torque
02... Intelligent sensorless
vector control (iSLV)

02

02

2CTRL I-SLV

A045 V/f gain setting

Sets voltage gain of the
inverter, range is 20. to 100.%

100.

100.

%

V-Gain 00100%

A046 Automatic torque boost

voltage gain

Sets torque boost voltage gain
of the inverter,
range is 0 to 255

100

100

A-Bst V 0100%

A246 Automatic torque boost

voltage gain, 2nd motor

Sets torque boost voltage gain
of the inverter,
range is 0 to 255

100

100

2ABst V 0100%

A047 Automatic torque boost

slip gain

Sets torque boost slip gain of
the inverter,
range is 0 to 255

100

100

A-Bst S1 00100%

A247 Automatic torque boost

slip gain, 2nd motor

Sets torque boost slip gain of
the inverter,
range is 0 to 255

100

100

2ABst S1 00100%

“A” Function

Run

Mode

Edit

Defaults

Func.

Code

Name /

SRW Display

Description

–FEF

(EU)

–FU

(USA)

Units