ModBus Data Listing

Appendix B

B–30

A094

Select method to switch
to Acc2/Dec2 profile

R/W Two options for switching

from 1st to 2nd accel/decel:
00... 2CH input from terminal
01... transition frequency

007Ch

0, 1

A294

Select method to switch
to Acc2/Dec2 profile,
2nd motor

R/W

007Dh

A095

Acc1 to Acc2 frequency
transition point

R/W Output frequency at which

Accel1 switches to Accel2,
range is 0.0 to 400.0 Hz

007Eh

0 to 4000

0.1 Hz

A295

Acc1 to Acc2 frequency
transition point, 2nd
motor

R/W

007Fh

A096

Dec1 to Dec2 frequency
transition point

R/W Output frequency at which

Decel1 switches to Decel2,
range is 0.0 to 400.0 Hz

0080h

0 to 4000

0.1 Hz

A296

Dec1 to Dec2 frequency
transition point, 2nd
motor

R/W

0081h

A097

Acceleration curve
selection

R/W Set the characteristic curve of

Acc1 and Acc2, two options:
00... linear
01... S-curve

0082h

0, 1

A098

Deceleration curve
selection

R/W Set the characteristic curve of

Acc1 and Acc2, two options:
00... linear
01... S-curve

0083h

0, 1

A101

[OI]–[L] input active
range start frequency

R/W The output frequency corre-

sponding to the current input
range starting point.
Range is 0.00 to 400.0 Hz

0084h

0 to 4000

0.1 Hz

A102

[OI]–[L] input active
range end frequency

R/W The output frequency corre-

sponding to the current input
range ending point.
Range is 0.00 to 400.0 Hz

0085h

0 to 4000

0.1 Hz

A103

[OI]–[L] input active
range start current

R/W The starting point for the

current input range.
Range is 0. to 100.%

0086h

0 to 100

1 %

A104

[OI]–[L] input active
range end current

R/W The ending point for the

current input range.
Range is 0. to 100.%

0087h

0 to 100

1 %

A105

[OI]–[L] input start
frequency enable

R/W Two options:

00... Use A101 start value
01... Use 0Hz

0088h

0, 1

Holding Registers for “A” Group Standard Functions

Func.

Code

Name

R/W

Description

Network Data

Reg.

Range

Res.