SJ200 Inverter

Appendix B

B–39

Note 1:

Assume that the inverter current rating is 10000 (for C041).

The following table lists the holding registers for the “H” Group Motor Constants.

C146

Terminal [12] ON delay

R/W Range is 0.0 to 100.0 sec.

00F4h

0 to 1000

0.1 sec

C147

Terminal [12] OFF
delay

R/W Range is 0.0 to 100.0 sec.

00F5h

0 to 1000

0.1 sec

C148

Output relay ON delay

R/W Range is 0.0 to 100.0 sec.

00F6h

0 to 1000

0.1 sec

C149

Output relay OFF delay

R/W Range is 0.0 to 100.0 sec.

00F7h

0 to 1000

0.1 sec

“C” Group Intelligent Terminal Functions

Func.

Code

Name

R/W

Description

Network Data

Reg.

Range

Res.

“H” Group Motor Constants

Func.

Code

Name

R/W

Description

Network Data

Reg.

Range

Res.

H003

Motor capacity

R/W Thirteen selections:

0..... 0.20 kW
1..... 0.37 kW
2..... 0.40 kW
3..... 0.55 kW
4..... 0.75 kW
5..... 1.10 kW
6..... 1.50 kW
7..... 2.2 kW
8..... 3.0 kW
9..... 3.7 kW
10... 4.0 kW
11... 5.5 kW
12... 7.5 kW

00D9h

0 to 12

H203

Motor capacity, 2nd
setting

R/W

00DAh

0 to 12

H004

Motor poles setting

R/W Four selections:

2 / 4 / 6 / 8

00DBh

2, 4, 6,

8

1 pole

H204

Motor poles setting, 2nd
motor

R/W

00DCh

2, 4, 6,

8

1 pole

H006

Motor stabilization
constant

R/W Motor constant (factory set),

range is 0 to 255

00DDh 0 to 255

1

H206

Motor stabilization
constant, 2nd motor

R/W

00DEh

0 to 255

1

H007

Motor voltage select

R/W Two selections, option codes:

00... 200V
01... 400V

00DFh

0, 1

H207

Motor voltage select,
2nd motor

R/W

00E0h

0, 1