Step-by-Step Basic Installation

In

v

e

rt

er Mounting

and Installation

2–20

Please use the terminal arrangement below corresponding to your inverter model.

NOTE: An inverter powered by a portable power generator may receive a distorted
power waveform, overheating the generator. In general, the generator capacity should be
five times that of the inverter (kVA).

CAUTION: Be sure that the input voltage matches the inverter specifications:
• Single/Three phase 200 to 240 V 50/60 Hz (up to 2.2kW) for NFEF/NFU models
• Three phase 200 to 240V 50/60Hz (above 2.2kW) for LFU models
• Three phase 380 to 480 V 50/60Hz for HFEF models

CAUTION: Be sure not to power a three-phase-only inverter with single phase power.
Otherwise, there is the possibility of damage to the inverter and the danger of fire.

Inverter models SJ200–002NFEF/NFU to –005NFEF/NFU

Inverter models SJ200–007NFEF to –022NFEF,
–007NFU to –037LFU, –004HFEF/HFU to –040HFEF/HFU

Jumper

Jumper

Chassis

Ground

Chassis

Ground

RB

U/T1

RB

U/T1 V/T2 W/T3

Inverter models SJ200–055HFEF/HFU, –075HFEF/HFU

Jumper

U/T1 V/T2 W/T3

Chassis

Ground

+1

+

L1

L2

+1

+

L1

L2 N/L3

L1

L2

L3

NFEF, NFU

LFU, HFEF, HFU

L3

+1

+

RB

L1

L2

V/T2 W/T3

N/L3

U/T1 V/T2 W/T3