Using Intelligent Input Terminals

Oper

ations

and Monitor

ing

4–20

External Trip

When the terminal [EXT] is turned ON, the inverter enters the trip state, indicates error
code E12, and stops the output. This is a general purpose interrupt type feature, and the
meaning of the error depends on what you connect to the [EXT] terminal. Even if the
[EXT] input is turned OFF, the inverter remains in the trip state. You must reset the
inverter or cycle power to clear the error, returning the inverter to the Stop Mode.

In the graph below, the [EXT] input turns ON during normal Run Mode operation. The
inverter lets the motor free-run to a stop, and the alarm output turns ON immediately.
When the operator initiates a Reset command, the alarm and error are cleared. When the
Reset is turned OFF, the motor begins rotation since the Run command is already active.

[EXT] terminal

RUN command [FW, RV]

[RS] terminal

Motor revolution speed

Alarm output terminal

t

free run

1
0

1
0

1
0

1
0

1
0

Option

Code

Terminal

Symbol

Function Name

Input

State

Description

12

EXT

External Trip

ON

When assigned input transitions OFF to ON,
inverter latches trip event and displays E12

OFF

No trip event for ON to OFF, any recorded trip
events remain in history until Reset

Valid for inputs:

C001, C002, C003, C004,
C005, C006

Required settings:

(none)

Notes:

If the USP (Unattended Start Protection) feature is
in use, the inverter will not automatically restart
after cancelling the EXT trip event. In that case, it
must receive either another Run command (OFF-to-
ON transition), a keypad Reset command, or an
[RS] intelligent terminal input signal.

1

2

3

4

5

6

L

PCS

Example (requires input configuration—
see page

3–41

):

See I/O specs on page

4–6

.

EXT