Hitachi SJ200 Series User Manual

Page 109

Advertising
background image

SJ200 Inverter

Conf

igur

ing

Dr
iv

e P

a

ra

m

e

ters

3–37

“B” Function

Run

Mode

Edit

Defaults

Func.

Code

Name /

SRW Display

Description

–FEF

(EU)

–FU

(USA)

Units

B080 [AM] analog signal

gain

Adjust of analog output at
terminal [AM],
range is 0 to 255

✘

100.

100.

—

AM-Adj 00100%

B082 Start frequency adjust-

ment

Sets the starting frequency for
the inverter output, range is 0.5
to 9.9 Hz

✘

0.5

0.5

Hz

fmin 0000.5Hz

B083 Carrier frequency

setting

Sets the PWM carrier (internal
switching frequency), range is
2.0 to 14.0 kHz

✘

5.0

5.0

kHz

Carrier 0005.0

B084 Initialization mode

(parameters or trip
history)

Select the type of initialization
to occur, two option codes:
00... Trip history clear
01... Parameter initialization
02... Trip history clear and
parameter initialization

✘

00

00

—

INIT Mode TRP

B085 Country code for initial-

ization

Select default parameter values
for country on initialization,
four options, option codes:
00... Japan version
01... Europe version
02... US version

✘

01

02

—

INIT Slct USA

B086 Frequency scaling

conversion factor

Specify a constant to scale the
displayed frequency for D007
monitor, range is 0.1 to 99.9

✔

1.0

1.0

—

Cnv Gain 0001.0

B087 STOP key enable

Select whether the STOP key
on the keypad is enabled, two
option codes:
00... enabled
01... disabled

✘

00

00

—

STP Key ON

Advertising