Hitachi SJ200 Series User Manual

Page 117

Advertising
background image

SJ200 Inverter

Conf

igur

ing

Dr
iv

e P

a

ra

m

e

ters

3–45

Note 1:

When using the Multi-speed Select settings CF1 to CF4, do not display
parameter F001 or change the value of F001 while the inverter is in Run Mode
(motor running). If it is necessary to check the value of F001 during Run
Mode, please monitor D001 instead of F001.

24

PIDC

PID Reset

ON

Resets the PID loop controller. The main conse-
quence is that the integrator sum is forced to
zero.

OFF

No effect on PID loop controller

27

UP

Remote Control
UP Function (motor-
ized speed pot.)

ON

Accelerates (increases output frequency) motor
from current frequency

OFF

Output to motor operates normally

28

DWN

Remote Control
DOWN Function
(motorized speed
pot.)

ON

Decelerates (decreases output frequency) motor
from current frequency

OFF

Output to motor operates normally

29

UDC

Remote Control Data
Clearing

ON

Clears the UP/DWN frequency memory by
forcing it to equal the set frequency parameter
F001. Setting C101 must be set=00 to enable this
function to work.

OFF

UP/DWN frequency memory is not changed

31

OPE

Operator Control

ON

Forces the source of the output frequency setting
(A001) and the source of the RUN command
(A002) to be from the digital operator

OFF

Source of output frequency set by (A001) and
source of run command set by (A002) is used

50

ADD

ADD frequency
enable

ON

Adds the A145 value (Add Frequency) to the
output frequency

OFF

Does not add the A145 value to the output
frequency

51

F-TM

Force Terminal
Mode

ON

Force inverter to use input terminals for output
frequency and Run command sources

OFF

Source of output frequency set by (A001) and
source of Run command set by (A002) is used

255

Not selected

ON

(input ignored)

OFF

(input ignored)

Input Function Summary Table

Option

Code

Terminal

Symbol

Function Name

Description

Advertising