SJ200 Inverter

Appendix B

B–37

C041

Overload level setting

R/W Sets the overload signal level

between 0% and 200% (from 0
to two times the rated current
of the inverter)

00BBh

0 to

20000

0.01 %

C042

Frequency arrival
setting for acceleration

R/W Sets the frequency arrival

setting threshold for the output
frequency during acceleration,
range is 0.0 to 400.0 Hz

00BCh

0 to 4000

*1

0.1 Hz

C043

Arrival frequency
setting for deceleration

R/W Sets the frequency arrival

setting threshold for the output
frequency during deceleration,
range is 0.0 to 400.0 Hz

00BDh

0 to 4000

0.1 Hz

C044

PID deviation level
setting

R/W Sets the allowable PID loop

error magnitude (absolute
value), SP - PV, range is 0.0 to
100%, resolution is 0.1%

00BEh

0 to 1000

0.1 %

C052

PID FBV function high
limit

R/W When the PV exceeds this

value, the PID loop turns OFF
the PID Second Stage Output,
range is 0.0 to 100.0%

00EAh

0 to 1000

0.1 %

C053

PID FBV function low
limit

R/W When the PV goes below this

value, the PID loop turns ON
the PID Second Stage Output,
range is 0.0 to 100.0%

00EBh

0 to 1000

0.1 %

C071

Communication speed
selection

NOTE: These network settings

are not accessible to ModBus.

Use the inverter keypad or

digital operator to edit. Refer to

“Network Communication

Settings” on page 3–50

.

00C0h

C072

Node allocation

00C1h

C074

Communication parity
selection

00C3h

C075

Communication stop bit
selection

00C4h

C076

Communication error
select

00ECh

C077

Communication error
time-out

00EDh

C078

Communication wait
time

00C5h

C081

O input span calibration

R/W Scale factor between the

external frequency command
on terminals L – O (voltage
input) and the frequency
output, range is 0.0 to 200.0%

00C7h

0 to 2000

0.1 %

“C” Group Intelligent Terminal Functions

Func.

Code

Name

R/W

Description

Network Data

Reg.

Range

Res.