B–20, Appendix b – Hitachi SJ200 Series User Manual

Page 234

Advertising
background image

ModBus Data Listing

Appendix B

B–20

Note 1:

ON usually when either the control circuit terminal board or a coil is ON.
Among intelligent input terminals, the control circuit terminal board is a high-
priority terminal. If the master cannot reset the coil ON status due to a trans-
mission line break, turn ON and OFF the control circuit terminal board to
make the coil OFF status.

Note 2:

The content of a transmission error is held until the error is reset. (The error
can be reset while the inverter is running.)

0014h

Alarm signal

R

0 .....Normal
1 .....Trip

0015h

PID deviation signal

R

0 .....OFF
1 .....ON

0016h

Overload signal

R

0017h

Frequency arrival signal
(set frequency or above)

R

0018h

Frequency arrival signal
(at constant speed)

R

0019h

Run Mode signal

R

001Ah

Data writing

R

0 .....Normal status
1 .....Writing

001Bh

CRC error

R

0 .....No error *2
1 .....Error

001Ch

Overrun error

R

001Dh

Framing error

R

001Eh

Parity error

R

001Fh

Check sum error

R

List of Coil Numbers

Coil

Number

Name

R/W

Description